The integrity poll hides lost DNP3 events: current values right, history wrong
DNP3 gives the master two views of an outstation. Static data (class 0) is the value of each point right now. Events (classes 1, 2 and 3) are the changes, each with its own timestamp, kept by the outstation until the master collects them. An integrity poll reads class 0 together with all event classes, and a master is expected to run one after a restart or an event buffer overflow. It is a good mechanism. It also hides a loss that is easy to miss.
The setup
A substation RTU with a class 1 buffer of 50 events. The master polls events every 60 seconds and runs an integrity poll every 10 minutes. At 10:01 a fault on the busbar makes 70 points change within 4 seconds, among them breaker CB-3, which opens, recloses, opens again and finally closes.
What happens
| Breaker CB-3 | In the field | In the SCADA history |
|---|---|---|
| 10:01:12 open | yes | yes |
| 10:01:13 close | yes | missing |
| 10:01:15 open | yes | missing |
| 10:01:16 close | yes | yes |
| 10:10:00 integrity poll (class 0) | closed | closed |
- The 70 changes do not fit in 50 slots. The outstation discards events and sets IIN2.3 EVENT_BUFFER_OVERFLOW on its next response.
- The master reacts correctly and runs an integrity poll. Every value on the display is right: CB-3 is closed.
- The SOE holds two of the four CB-3 operations. The reclose cycle that tells a protection engineer what happened is gone, and nothing on the operator's screen says so.
How to recognise it
- IIN2.3 in the traffic, even once. Every overflow is a gap in the history, whatever the display shows afterwards.
- A static value that disagrees with the last event for that point: the integrity poll reports a state the event stream never moved to. Some masters log this as an "unreported change"; most stay silent.
- Event counts that are suspiciously round right before an overflow: the buffer size, every time.
What to change
- Size the event buffer for the worst disturbance, not the average rate, and give protection-relevant points their own class.
- Collect events faster during disturbances: unsolicited reporting, or a shorter event poll.
- Have the master flag the SOE as incomplete for the period of an overflow, so nobody analyses a fault on partial data without knowing it.
Try it on your own capture